4-40 WANsuite 7105
Figure 4.32
SCADA Service Details Screen
Message Size
Maximum number of characters to buffer before sending a frame.
Values: 01024
Default: 256
Idle Character Delay
Maximum number of idle character time to wait before sending a frame.
Values: 065535
Default: 10
Input Terminator
Decimal value of the character that terminates a message before sending a
frame.
Values: 0255
Default: 0
Data Direction
Data direction that the port will support. If set to “Input,” the port will only
accept incoming data and will not transmit data. If set to “Output,” the port
will ignore any incoming data. If set to “Both,” the port will process all data.
Values: Input, Output, Both
Default: Both
SCADA Loopback
Determines if and where SCADA will loopback received data.
Values: None, Loopback to Network, Loopback to Port
Default: None
The table below these parameters displays the SCADA statistics. You can
clear all SCADA statistics by selecting the “SCADA Clear Statistics” prompt
at the bottom of the screen.
Select the “SCADA Device List” prompt to bring up a screen that shows the
mapping between SCADA devices and endpoints (Figure 4.33).